Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T20CM02684
Parcel: 11615088L

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM02684
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/27/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Completed