Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T20CM02684
Parcel: 11615088L

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM02684
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/27/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Previous Comment 1; Sheet G2.1; Code Plan; Project Data: The "maximum exit access travel distance (sprinkler system) still indicates 300'. Please revise.
2. Previous Comment 1; Sheet G2.1; Code Plan: Please measure the exit access travel distance per the IBC Section 1017.3. The travel distance measurement must be along the natural and unobstructed path of horizontal and vertical egress travel (not diagonal). Please revise.
3. Sheet A7.1; Elevation 22: Please locate the side wall horizontal grab bar per the ICC/ANSI Figure 604.5.1. In addition, include a back wall elevation with the horizontal grab bar.
4. General: Please include all drawings in the new submittal.
5. General: Please provide written responses to all review comments.