Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T20CM02671
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/30/2020 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 05/19/2020 | LOREN MAKUS | ENGINEERING | REVIEW | Passed | |
| 05/21/2020 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL FROM: Steve Shields Section Manager PROJECT: PPEP Benson Hwy - Solar Parking Covers T20CM02671 Canopy Plans (1st Review) TRANSMITTAL DATE: May 21, 2020 1. The solar canopy plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. Until DP20-0049 is approved the solar canopy plans cannot be approved. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |
| 05/29/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Verify compliance with NEC 690.13C for the PV disconnect switch. 2. Provide more detail including hardware for the PV module grounding to the steel structure. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |
| 06/03/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/20/2020 | SBEASLE1 | OUT TO CUSTOMER | Completed |