05/04/2020 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T20CM02653
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

STRUCTURAL PLANS:

1. Show the block column material with size, R301.1.
2. Provide a complete roof framing plan with beams sized with appropriate load carrying capacity, R301.1.
3. Provide a rafter layout, or truss plan (may be noted as a delayed submittal), R301.1.

PLUMBING PLANS:

1. Notate and specify all piping materials, P2608. Include sizes of gas, water and sewer pipes.
2. Show all drainage fixtures (sink) with connection to the public sewer system, P2602.1.

If you have any questions, please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review
05/19/2020 ANDREW CONNOR NPPO REVIEW Passed
05/20/2020 LOREN MAKUS ENGINEERING REVIEW Passed
05/21/2020 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Section Manager

PROJECT: T20CM02653
6802 E Edgemont St
Gazebo w/ Kitchen
Residential (1st Review)

TRANSMITTAL DATE: May 21, 2020

The Gazebo plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

This site is located in the R-1 zone (UDC 4.7.1). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. 10.

Indicate the name of the Owner and the property address.
Clearly show the location of the square footage of the new structure(s) and their use.
Indicate the maximum structure height.
Show locations of utility lines for water, sewer, electric and gas.
Indicate the zoning of the property and of the surrounding properties.
Provide a legal description of the property (i.e. the subdivision name and lot number or metes and bounds legal if not in a subdivision)

Provide a dimension from the center line of Edgemont Street to the curb and a dimension from the curb to the street property line. The distance from center line of Edgemont Street to the back of curb is 18', and from the back of curb to property lines is 7'.

The drawing shall be drawn to an engineering scale, i.e. 1" = 10'

Provide a lot coverage calculation on the plot plan

Provide the parcel dimensions on the plot plan.