Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T20CM02651
Parcel: 13314236C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM02651
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/11/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet G000; Project Summary (Plumbing Fixtures): No indication of a drinking fountain (hi/low or single point-of-use) is made in this analysis. Please indicate on the drawings the requirements for a drinking fountain are met (IBC Table 2902.1), and show that location on the plan. Or indicate the drinking fountain location meets the IBC Section 2902.5 (show this drinking fountain location and indicate the travel distance from the tenant space to that fountain).
2. Sheet G101; Egress Plan: Please verify the doors at Restrooms 104 and 105 do not reduce the required exit width by more than 1/2 (IBC Section 1005.7.1). Per the IBC Table 1020.2, the required minimum exit width is 36". Please indicate on the plan the exit width when those doors are open into the corridor.
3. Sheet G404; Elevation F: Please add the vertical grab bar in the restroom per the ICC/ANSI Figure 604.5.1.
4. Sheet A101; Elevation 15(C): Please add the vertical grab bar in the restroom per the ICC/ANSI Figure 604.5.1.
5. General: Please provide written responses to all review comments.
05/11/2020 MARTIN BROWN FIRE REVIEW Approved
05/12/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide a metering faucet for the relocated lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09
05/12/2020 ROBERT SHERRY WATER REVIEW Completed
05/12/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Verify that restroom 105 has an exhaust fan.
06/05/2020 ARUIZ1 ELECTRICAL-COMMERCIAL REVIEW Needs Review