Permit Number: T20CM02646
Parcel: 116141350

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T20CM02646
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/08/2020 ANDREW CONNOR NPPO REVIEW Passed
05/08/2020 LOREN MAKUS ENGINEERING REVIEW Passed
05/15/2020 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Section Manager

PROJECT: T20CM02646
2040 W Calle Placida
Detached Porch in Front Yard.
Residential (1st Review)

TRANSMITTAL DATE: May 15, 2020

The room addition plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

This site is located in the R-1 zone (UDC 4.7.1). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. 10.

1. Provide a dimension from the center line of Calle Placida to the curb and a dimension from the curb to the street property line.

2. Provide a lot coverage calculation on the plan.

3. The parcel dimensions shown on the plan are not correct. Per the final plat the north and south property line dimension is 80'.

4. Per UDC Article 6.6.3.B a detached accessory structure, Porch, is not allowed in the front yard a Board of Adjustment for Variance is required or the structure must be connected to the main dwelling with a minimum 5'-0" wide porch like structure that can support a 20 lb live load.

5. Per UDC Article 6.4.5.C.1.a the minimum street perimeter yard setback is 20'-0". If you elect to go through the Board of Adjustment the setback can be reduced via this process. If you elect to connect the porch to the house a Design Development Option (DDO) will need to be processed and approved prior to approval of these plans.

Residential plot plan requirements can be found at https://www.tucsonaz.gov/pdsd/all-application-forms-submittal-requirements.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
05/18/2020 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change SHOW TWO #4 REBAR EACH-WAY AT THE FOOTER BASE.