Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T20CM02635
Parcel: 12212010B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM02635
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/29/2020 MARTIN BROWN FIRE REVIEW Approved
05/05/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide structural calculations for the mounting shelf for the water heater to show that the water heater will be safely supported from the building structure. Reference: Section 301.2, IPC 2018.
2. Verify that the vent for the grease interceptor can rise vertically (i.e. at least 45 degrees above horizontal) to at least 6" above the flood rim of the interceptor prior to running horizontally. Reference: Section 905.4, IPC 2018.
05/05/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
05/05/2020 LOREN MAKUS ENGINEERING REVIEW Passed
05/05/2020 ROBERT SHERRY WATER REVIEW Completed
05/21/2020 STEVE SHIELDS ZONING REVIEW Approved
05/22/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
05/25/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/25/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed