Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM02635
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/29/2020 | MARTIN BROWN | FIRE | REVIEW | Approved | |
05/05/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide structural calculations for the mounting shelf for the water heater to show that the water heater will be safely supported from the building structure. Reference: Section 301.2, IPC 2018. 2. Verify that the vent for the grease interceptor can rise vertically (i.e. at least 45 degrees above horizontal) to at least 6" above the flood rim of the interceptor prior to running horizontally. Reference: Section 905.4, IPC 2018. |
05/05/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
05/05/2020 | LOREN MAKUS | ENGINEERING | REVIEW | Passed | |
05/05/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
05/21/2020 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
05/22/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
05/25/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
05/25/2020 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |