Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T20CM02634
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/14/2020 | SAMUEL ROGERS | ZONING | REVIEW | Reqs Change | SEE COMMENTS T20CM01566, DUPLICATE PERMIT CREATED |
| 05/14/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide a complete electrical plan with a one line diagram including the following information; (a) Clarify load calcs. Is the calculated load for the existing 3 units a total of 66 amps? (b) The panel schedule is calling the House Panel 'B', and the line diagram is calling it 'A'. Please clarify. (c) Indicate AIC ratings for the service equipment and downstream equipment. (d) Show conduit, conductor sizes and types for all the feeds shown in the line diagram. Also include the feeders extended to the new location of the service disconnects. 2. Provide a complete electrical floor plan showing all the equipment, receptacles, lighting connecting to the new house panel. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/04/2020 | ARUIZ1 | OUT TO CUSTOMER | Completed |