Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T20CM02633
Parcel: 133381990

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM02633
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/10/2020 STEVE SHIELDS ZONING REVIEW Approved
09/22/2020 JPEELDA1 FIRE REVIEW Approved Per the 2018 International Fire Code:
A residence must be within 600' of a fire hydrant.
A residence deeper than 150' on a lot must provide a fire department approved access road, with a turnaround.
The size of the existing building plus additions would require a commercial fire flow from the hydrant, if it was close enough.
The only way to mitigate these code issues would be to install a residential fire sprinkler system. Please add a note to the cover sheet that a sprinkler system will be installed.
09/22/2020 JPEELDA1 FIRE REVIEW Approved Raymond stated that they will be adding fire sprinklers and that the turn around will meet the requirements. I added the notes with his permission and added the notes to the drawings.
10/26/2020 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Completed