05/21/2020 MARTIN BROWN FIRE REVIEW Reqs Change Per the 2018 International Fire Code:
A residence must be within 600' of a fire hydrant.
A residence deeper than 150' on a lot must provide a fire department approved access road, with a turnaround.
The size of the existing building plus additions would require a commercial fire flow from the hydrant, if it was close enough.
The only way to mitigate these code issues would be to install a residential fire sprinkler system. Please add a note to the cover sheet that a sprinkler system will be installed.