Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T20CM02628
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/11/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 01/12/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 12/08/2020 | JGARCIA1 | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. The minimum exhaust requirement for a kitchen is 100 CFM intermittent or 25 CFM continuous; where did the "25 CFMs/100 S. F." come from? Reference: Section 403.3.2.3, IMC 2018. [Initial comment: Provide specifications for the kitchen exhaust fan. Reference: Table 403.3.1.1, IMC 2018.] 2. The minimum exhaust requirement for a bathroom or toilet room is 50 CFM intermittent or 20 CFM continuous; where did the "20 CFMs/50 S. F." come from? Reference: Section403.3.2.3, IMC 2018. [Initial comment: Provide specifications for the bathroom exhaust fans. Reference: Table 403.3.1.1, IMC 2018.] |
| 12/08/2020 | JGARCIA1 | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Revise the water pressure calculations to include the pressure drop caused by the reduced pressure backflow preventer. [Initial comment: Clarify the method used to determine the size of the water distribution pipes. If the method used is from Section E201, IPC 2018, show the water pressure adjustments used to select the appropriate pipe sizing table (e.g. Section E201.1, IPC 2018). Reference: Section 604.1, IPC 2018.] 2. The water heater detail did not include the hot water circulation system required by Section 607.2.1, IPC 2018 for R-4 occupancies with a hot water distribution system having a developed length in excess of 50-feet. [Initial comment: Provide a detail of the water heater installation, including the excess pressure relief, expansion tank, vacuum relief or other anti-siphon device, safety pan, and valves. Reference: Sections 503.1, 504, 606.1, 607.2, and 607.3, IPC 2018.] |