Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T20CM02628
Parcel: 128140700

Address:
5231 E 19TH ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM02628
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/21/2020 ROBERT SHERRY PLUMBING-RESIDENTIAL REVIEW Reqs Change 1. Revise the water pressure calculations to include the pressure drop caused by the reduced pressure backflow preventer. [Initial comment: Clarify the method used to determine the size of the water distribution pipes. If the method used is from Section E201, IPC 2018, show the water pressure adjustments used to select the appropriate pipe sizing table (e.g. Section E201.1, IPC 2018). Reference: Section 604.1, IPC 2018.]
2. The water heater detail did not include the hot water circulation system required by Section 607.2.1, IPC 2018 for R-4 occupancies with a hot water distribution system having a developed length in excess of 50-feet. [Initial comment: Provide a detail of the water heater installation, including the excess pressure relief, expansion tank, vacuum relief or other anti-siphon device, safety pan, and valves. Reference: Sections 503.1, 504, 606.1, 607.2, and 607.3, IPC 2018.]
08/21/2020 ROBERT SHERRY MECHANICAL-RESIDENTIAL REVIEW Reqs Change 1. The minimum exhaust requirement for a kitchen is 100 CFM intermittent or 25 CFM continuous; where did the "25 CFMs/100 S. F." come from? Reference: Section 403.3.2.3, IMC 2018. [Initial comment: Provide specifications for the kitchen exhaust fan. Reference: Table 403.3.1.1, IMC 2018.]
2. The minimum exhaust requirement for a bathroom or toilet room is 50 CFM intermittent or 20 CFM continuous; where did the "20 CFMs/50 S. F." come from? Reference: Section403.3.2.3, IMC 2018. [Initial comment: Provide specifications for the bathroom exhaust fans. Reference: Table 403.3.1.1, IMC 2018.]
08/21/2020 ROBERT SHERRY WATER REVIEW Completed
09/17/2020 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Passed
09/18/2020 STEVE SHIELDS ZONING REVIEW Approved
12/08/2020 JGARCIA1 ELECTRICAL-RESIDENTIAL REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
12/08/2020 JGARCIA1 APPROVAL SHELF Completed
12/08/2020 JGARCIA1 OUT TO CUSTOMER Completed
12/08/2020 JGARCIA1 REJECT SHELF Completed