Review Date Reviewer's Name Type of Review Description Status Comments
04/30/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change The equipment submittal shows a sixth AC unit (3-ton split system) to be used for the stockroom. Provide heating/cooling load calculations for the stockroom system.

Final Status