Permit Number: T20CM02556
Parcel: 11615077C

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM02556
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/26/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Comment not resolved, provide revised drawings. [Initial comment: Provide metering faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.]
08/26/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Comment not resolved, provide revised drawings. [Initial comment: Condensate drains may not terminate over a roof drain or gutter unless the roof drain or gutter terminates at or below grade in an area capable of absorbing the condensate flow without surface drainage. Reference: Section 307.2.1, IMC 2018, as amended by the City of Tucson.]
2. Comment not resolved, provide revised drawings. [Initial comment: Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted (i.e. all of the air supplied to each restroom is to be exhausted during the hours of operation even if the lights are off). Reference: Section 403.2.1 (4), IMC 2018.]
3. Comment not resolved, provide calculations. [Initial comment: Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified new HVAC units. Reference: Section C403.1.1 and C502.2.3, IECC 2018.]
4. Comment not resolved, provide calculations. [Initial comment: Demonstrate energy code compliance for the alteration to the building envelope using calculations based on the current code (e.g. COMcheck). Reference: Sections C503.1 and C503.3, International Energy Conservation Code 2018.]
08/28/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. No response letter found or plan revisions concerning the electrical plan review comments in this 2nd plan submittal.
2. No electrical plans.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements, 2012 Tucson/Pima County Outdoor Lighting Code.
09/02/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. General: All architectural sheets must be sealed, signed, and dated by a registered professional.
2. General: Sheet ME1 is not included in this set, but listed in the Sheet Index.