Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM02556
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/18/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 05/18/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide evidence on the plans that the proposed exterior lighting fully complies with the Outdoor Lighting Code. See section 104 for plan submittal requirements. 2. Provide lighting plans with the following information on the plans; (a) Provide a complete luminaire schedule. (b) Size of the parcel in acres. (c) See table 401.1, lighting area and option and indicate this information in the lighting site plan, also showing the locations and types of all exterior luminaires including existing. (d) 402.1 (light source color temperature requirements), shielding requirements, etc . (e) Provide calcs for total lumens allowed and total lumens proposed per acre including existing, for Full Cut Off and Unshielded per table 401.1. (f) Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2. (g) Specify any exceptions used. (h) Curfew lighting controls If applicable. Do not confuse the Outdoor Lighting Code with the IECC. 3. Provide complete compliance with the 2018 IECC. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements, 2012 Tucson/Pima County Outdoor Lighting Code. |
| 05/18/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Condensate drains may not terminate over a roof drain or gutter unless the roof drain or gutter terminates at or below grade in an area capable of absorbing the condensate flow without surface drainage. Reference: Section 307.2.1, IMC 2018, as amended by the City of Tucson. 2. Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted (i.e. all of the air supplied to each restroom is to be exhausted during the hours of operation even if the lights are off). Reference: Section 403.2.1 (4), IMC 2018. 3. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified new HVAC units. Reference: Section C403.1.1 and C502.2.3, IECC 2018. 4. Demonstrate energy code compliance for the alteration to the building envelope using calculations based on the current code (e.g. COMcheck). Reference: Sections C503.1 and C503.3, International Energy Conservation Code 2018 |
| 05/18/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Provide metering faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09. |
| 05/21/2020 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 06/30/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A1.1; Floor Plan: At the west wall of this space (at Key Note 4), a detail references 4/A4.1. Please revise that reference. 2. Sheet A1.1 (Floor Plan); Sheet A4.2 (Detail 12): Detail 12 references the Floor Plan for the interior wall type. That wall type is not indicated on the Floor Plan. Please provide. 3. Sheet A4.2; Key Notes: Note 2 references structural drawings for the attachment of the wall framing and bracing to the roof structure. Please revise that reference, and add details on this sheet for the wall and bracing condition. 4. Sheet A4.2; Detail 6: Should there be a lintel indicated on this detail at the wall opening? Please indicate on the Floor Plan (Sheet A1.1) and Detail 6/A4.2 as required. 5. General: Are structural sheets missing in this submittal? Please verify. 6. General: Please provide written responses to all review comments. |