Permit Number: T20CM02555
Parcel: 126040300

Review Status: Active

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T20CM02555
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
04/27/2020 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change Provide the BTU demand of each appliance, total demand, and total developed length from meter to the most remote appliance on the system, and verify the size of the supply pipe for the connected demand, G2413.3 & Table G2413.4(1).
RESUBMIT WITH THE CORRECT DEVELOPED LENGTH. REMOVE THE RANGE BRANCH OR SHOW A 1" PIPE FROM THE METER TO FIRST BRANCH TEE.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/24/2020 ANY REJECT SHELF RECEIVED