Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T20CM02538
Parcel: 11918027A

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T20CM02538
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/27/2020 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
06/24/2020 ARAMIRE4 OUT TO CUSTOMER Approved