Permit Number: T20CM02511
Parcel: 122160020

Address:
3514 E GRANT RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM02511
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/23/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide a plumbing plan for the installation of the new sinks.
04/23/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide a path for air return from the new room.
04/23/2020 MARTIN BROWN FIRE REVIEW Reqs Change Mathmatical error in computation of occupant load. Please review and revise.
04/23/2020 ROBERT SHERRY WATER REVIEW Completed
04/24/2020 NICHOLAS ROSS ZONING REVIEW Reqs Change Correct zoning classification on first sheet
04/24/2020 NROSS1 ENGINEERING REVIEW Passed
04/24/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
04/24/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet TS1; Code Review: Please revise the occupant load.
2. Sheet A1.0; Floor Plan: Please indicate the name/use of each room on the plan.
3. General: Please provide written responses to all review comments.
04/24/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed