Permit Number: T20CM02483
Parcel: 12404100A

Address:
930 E 2ND ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM02483
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/23/2020 ELISA HAMBLIN ZONING REVIEW Approved
04/23/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
04/23/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
04/23/2020 EHAMBLI1 ENGINEERING REVIEW Passed
04/23/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet S1.01 (Isolated Footing Schedule); Structural Calculations (Pages 53 and 57): The calculations indicate a 8'-9" square x 28" deep column footing, while the Footing Schedule indicates a 8'-9" square x 24" deep footing. Please coordinate.
2. Sheet S1.01 (Isolated Footing Schedule); Structural Calculations (Page 57): The calculations indicate 13-#6 bottom bars each way, while the Footing Schedule indicates 12-#6 top and bottom each way. Please coordinate.
3. Sheet S2.01 (Section 105); Structural Calculations (Page 67): The calculations indicate 6 anchor bolts located 2" from the edges of the base plate, while the Section indicates 8 bolts located 3" from the edges of the base plate. Please coordinate.
4. General: Please provide a Special Inspection Certificate with Parts A and B completed. It is located at the website www.tucsonaz.gov/PDSD.
5. General: Please provide written responses to all review comments.
04/23/2020 ROBERT SHERRY WATER REVIEW Completed
04/23/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
04/23/2020 MARTIN BROWN FIRE REVIEW Approved
04/23/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed