Permit Number: T20CM02468
Parcel: 12417157B

Address:
1050 E 19TH ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM02468
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/22/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/22/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
04/22/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide compliance with the 2018 IECC for the interior lighting.
2. Assign branch circuit and panel designations for the new or replaced lighting.
3. Provide a complete panel schedule for the new panel 'EV'.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.
04/22/2020 MARTIN BROWN FIRE REVIEW Approved
04/22/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet G2; Code Reference Plan: Please clarify on the plan the circled numbers at each exit are the number of occupants exiting at that location.
2. Sheet G2; IBC Review: Please indicate the required drinking fountains on the plan.
3. Sheet A2; Detail Floor Plan; Wall Types: On Wall Types W1, W2, W4, and W5, please indicate the stud spacing. Provide details for the bracing of the interior partitions in order to meet the IBC Section 1607.15 requirements. Include bracing size, spacing, and connection at the top of the partition and at the existing framing above.
4. General: Please provide written responses to all review comments.
04/22/2020 ROBERT SHERRY WATER REVIEW Completed
04/22/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
04/28/2020 EHAMBLI1 ENGINEERING REVIEW Passed
04/28/2020 ELISA HAMBLIN ZONING REVIEW Approved