Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T20CM02464
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/22/2020 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 04/22/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide overcurrent protection for the feeders and panel 'OP-P1' per NEC 408.36. 2. Provide complete panel schedule for panel 'OP-HV1'. 3. Verify that there is a maintenance receptacle on the roof for the mechanical equipment. NEC 210.63. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |
| 04/23/2020 | ELISA HAMBLIN | ZONING | REVIEW | Reqs Change | Appears generator will remove required parking needed on site per D09-0036, which required 154 spaces on site with 154 provided. Recommend moving generator to location which will not impact required site development features (not in parking, pedestrian or required landscape area). |
| 04/29/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/21/2020 | ARUIZ1 | OUT TO CUSTOMER | Completed |