Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T20CM02456
Parcel: 10512030D

Address:
4022 N ORACLE RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM02456
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/26/2020 ROBERT SHERRY WATER REVIEW Completed
05/26/2020 MARTIN BROWN FIRE REVIEW Approved
05/27/2020 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Reqs Change BUILDING – COMMERCIAL
1. Please respond to all review comments in writing.
2. On sheet T100 the Occupancy Group under Building & Construction Code Data could be “Business B” as this facility is a “food processing establishment and commercial kitchen not associated with restaurants, cafeterias and similar dining facilities not more than 2,500 SF in area.” Changing the occupancy classification to B also allows you to claim the unisex restroom exception 4 under 2018 IBC P2902.2. Otherwise, two separate restrooms will be required per P2902.2 as exceptions do not apply to A-2 occupancy with 18 occupants (public + staff).
3. Provide structural calculations sealed by the EOR for roof structure modifications. Ref. 2018 IBC 107.2.1.
05/27/2020 PIMA COUNTY ELECTRICAL-COMMERCIAL REVIEW Completed
05/28/2020 PIMA COUNTY PLUMBING-COMMERCIAL REVIEW Reqs Change PLUMBING – COMMERCIAL
1. Please respond to all review comments in writing.
2. The Fixture Unit Schedule on sheet P001 references 2012 IPC. The adopted Code in Tucson is the 2018 IPC. Revise Code edition and references.
3. The Gas Demand schedule on sheet P001 references the 2012 IFGC. The adopted Code in Tucson is the 2018 IFGC. Revise Code edition and references.
4. The Grease Interceptor Sizing schedule on sheet P002 references the 2012 IPC. The adopted Code in Tucson is the 2018 IPC with City of Tucson amendment for new Section 1003.3 Grease Interceptors. Revise Code edition and references. This amendment to the 2018 IPC 1003.3 requires that the minimum size of the hydromechanical grease interceptor shall be no smaller than 25 gallon per minute with a 50-lb grease capacity.
5. The three-compartment sink 1/P200 shall have three trapped and vented individual drains to prevent cross contamination from possible blockage of a single drain termination. All three drain pipes shall discharge into the floor sink through an air gap. Ref. 2018 IPC 801.2.
05/28/2020 PIMA COUNTY MECHANICAL-COMMERCIAL REVIEW Reqs Change MECHANICAL – COMMERCIAL
1. Please respond to all review comments in writing.
2. The Ventilation Air Calculation table on sheet M001 references 2012 IMC. The adopted Code in Tucson is the 2018 IMC. Revise Code edition and references.
3. The Walk-in Cooler Schedule on sheet M001 references 2012 IMC. The adopted Code in Tucson is the 2018 IMC. Revise Code edition and references.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/28/2020 JGARCIA1 APPROVAL SHELF Passed
05/28/2020 JGARCIA1 OUT TO CUSTOMER Completed
05/28/2020 JGARCIA1 REJECT SHELF Completed