Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T20CM02434
Parcel: 13317064C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM02434
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/27/2020 SARAH MEGGISON ZONING REVIEW Passed
05/27/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide information regarding the nature of the exhaust from the mixing room. Explain how Section 403.2.1 (4), IMC 2018 applies to this installation.
2. Clarify the "void space" south of room 215; is it a fire-rated shaft?
05/27/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
05/27/2020 ROBERT SHERRY WATER REVIEW Completed
05/27/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A2; Reflected Ceiling Plan: Please indicate the exit lighting on this plan.
05/27/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
05/27/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/01/2020 MRESS1 ENGINEERING REVIEW Passed
06/02/2020 MARTIN BROWN FIRE REVIEW Approved