Permit Number: T20CM02426
Parcel: 12901035M

Review Status: Completed

Review Details: 3RD PARTY REVIEW - COMMERCIAL

Permit Number - T20CM02426
Review Name: 3RD PARTY REVIEW - COMMERCIAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/30/2020 MARTIN BROWN FIRE REVIEW Reqs Change Please add list of deferred submittals to cover sheet. This should include fire sprinklers, fire sprinkler underground supply piping, and fire alarm system.
Please indicate the proposed location of the fire sprinkler underground supply piping.
05/08/2020 ROBERT SHERRY WATER REVIEW Reqs Change 1. Clarify the water service to the new building. Is the existing 2" water meter serving just the new apartment building or multiple buildings? Why is a 1-1/2" water meter noted in the water calculations?
2. Revise the static lift used in the water calculations to equal the height of the highest water outlet.
3. 288 water fixture units is equivalent to about 83 GPM, not 20 GPM.
05/19/2020 LOREN MAKUS ENGINEERING REVIEW Approved
05/21/2020 STEVE SHIELDS ZONING REVIEW Approved
06/17/2020 STANTEC 3RD PARTY REVIEW-COMMERCIAL AT 3RD PARTY OFFICE Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/17/2020 JGARCIA1 REJECT SHELF Passed
06/17/2020 JGARCIA1 APPROVAL SHELF Completed
06/17/2020 JGARCIA1 OUT TO CUSTOMER Completed