Permit Review Detail
Review Status: Completed
Review Details: 3RD PARTY REVIEW - COMMERCIAL
Permit Number - T20CM02426
Review Name: 3RD PARTY REVIEW - COMMERCIAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/30/2020 | MARTIN BROWN | FIRE | REVIEW | Reqs Change | Please add list of deferred submittals to cover sheet. This should include fire sprinklers, fire sprinkler underground supply piping, and fire alarm system. Please indicate the proposed location of the fire sprinkler underground supply piping. |
| 05/08/2020 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | 1. Clarify the water service to the new building. Is the existing 2" water meter serving just the new apartment building or multiple buildings? Why is a 1-1/2" water meter noted in the water calculations? 2. Revise the static lift used in the water calculations to equal the height of the highest water outlet. 3. 288 water fixture units is equivalent to about 83 GPM, not 20 GPM. |
| 05/19/2020 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 05/21/2020 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 06/17/2020 | STANTEC | 3RD PARTY REVIEW-COMMERCIAL | AT 3RD PARTY OFFICE | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/17/2020 | JGARCIA1 | REJECT SHELF | Passed |
| 06/17/2020 | JGARCIA1 | APPROVAL SHELF | Completed |
| 06/17/2020 | JGARCIA1 | OUT TO CUSTOMER | Completed |