Permit Number: T20CM02412
Parcel: 109224450

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM02412
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/27/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The project code review on sheet TS1 states that 3 water closets and 3 lavatories have been provided for this suite. Coordinate code review with the architectural and plumbing designs. Reference: Section 107.2.1, IBC 2018.
05/27/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. The submitted COMcheck mechanical compliance certificate is for a building alteration. As a shell building with no air conditioning, this activity is considered to be new construction based on the 2018 IECC. Reference: Section 503.2, IECC 2018.
2. Provide an economizer for HP-2 or increase the unit's energy efficiency to at least 110% of the minimum energy efficiency shown in Table C403.3.2(2), IECC 2018.
05/27/2020 MARTIN BROWN FIRE REVIEW Approved
05/27/2020 ROBERT SHERRY WATER REVIEW Completed
06/01/2020 MALLORY RESS ZONING REVIEW Approved
06/01/2020 MRESS1 ENGINEERING REVIEW Passed
06/01/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
06/03/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet TS1; Project Code Review: The exiting calculations indicate one exit is provided, while Sheet A1.1 Egress Plan indicates an exit in the Break Room. Please verify this is not an exit door location.
2. Sheet TS1; Applicable Codes: Please revise the NEC to the 2017 Edition.
3. Sheet A1.0; Wall Types: Three different wall types are indicated on this sheet. Please add a wall type indicator for each and tag all walls on the Floor Plan with the specific wall type.
4. Sheet A1.0; Wall Detail 1: This detail indicates ceiling joists for GWB ceilings. Is this typical at all interior walls? If yes, please indicate in a note on the detail. If not, indicate on the Reflected Ceiling Plan (Sheet A2.0) all areas that have ceiling joists.
5. Sheet A1.1; Means of Egress Notes: Please add a note referencing the IBC Table 1006.2.1 for the allowable common path of egress travel (100').
6. Sheet A1.1; Egress Plan: Per the IBC Section 1017.3, the exit access travel distance shall be measured from the most remote point of each room (X-Ray Room) along the natural and unobstructed path of horizontal and vertical egress travel. Please revise this plan.
7. Sheet A2.0; Ceiling Legend: The 5/8" GWB ceiling references Detail 3/A2.0. Please revise that detail reference.
8. General: PLease provide written responses to all review comments.
06/03/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed