Permit Number: T20CM02351
Parcel: 117121930

Address:
40 E CONGRESS ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM02351
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/15/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
05/15/2020 ROBERT SHERRY WATER REVIEW Completed
05/18/2020 MARTIN BROWN FIRE REVIEW Approved
05/18/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
05/28/2020 LOREN MAKUS ENGINEERING REVIEW Passed
05/29/2020 STEVE SHIELDS ZONING REVIEW Approved
06/09/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
06/26/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A1.0 (Second Floor Plan); Sheet A8.0 (Enlarged Plan 6): The enlarged plan indicates the Fifth Floor Coffee Station, while the Second Floor Plan indicates this Coffee Station. Please clarify.
2. Sheet A1.0; Second Floor Plan: The east walls of spaces 218, 219, 220, 221, 222, and 223 are glass walls. Please reference Sheet A5.0 for the elevations of these walls.
3. Sheet A1.0; Second Floor Plan: The north wall of spaces 208, 209, and 210, and the south wall of space 202 are glass walls, but indicate in the Room Finish Schedule (Sheet A6.0) they are painted. Please verify.
4. Sheet A5.1; Enlarged Plan 1: Elevations 2, 3, 4, and 5 on the enlarged plan reference Sheet A9.0. Please revise that reference.
5. Sheet A5.1; Elevations 2 and 4: A note on these elevations references Sheet A9.0. Please revise that reference.
6. Sheet A7.0; Enlarged Plan 1: Elevations 2, 3, and 4 on the enlarged plan reference Sheet A8.17. Please revise that reference.
7. Sheet A8.0; Enlarged Plan 6: An elevation on the enlarged plan references Sheet A8.16. Please revise that reference.
8. Sheet A8.0; Enlarged Plan 1: Elevations 2, 3, 4, and 5 on the enlarged plan reference Sheet A8.16. Please revise that reference.
9. Sheets AV-1.0, AV-2.0, ID1.0, and ID2.0: These sheets are not stamped by a registered professional and lack a title block. Please revise.
10. General: Please provide written responses to all review comments.
06/26/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed