Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T20CM02335
Parcel: 11720016H

Address:
100 S CHURCH AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM02335
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/21/2020 SAMUEL ROGERS ZONING REVIEW Reqs Change RNA review required for exterior facade work. When complete, contact me for an "over-the-counter" review or sign into our Virtual Service Counter online.
Elisa Hamblin
elisa.hamblin@tucsonaz.gov
04/21/2020 ROBERT SHERRY WATER REVIEW Completed
04/21/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please verify that there are maintenance receptacles and a lighting outlet where applicable for the mechanical equipment on the roof and for the Fan Coils. NEC 210.63, 210.70.A(3).
04/21/2020 SROGERS2 ENGINEERING REVIEW Passed
04/21/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A1.1; Egress Floor Plans: The maximum travel distance allowed to an exit indicates 300' for a B Occupancy, and 250' for an M Occupancy. The travel distances are not indicated on each floor plan. Please provide for all exit access paths.
2. Sheet D2.1; Demolition Plan Keynotes: Note 11 was not located on this plan. Please verify.
3. Sheets D2.1, D2.2, and D2.3; Demolition Plan Keynotes: Please indicate that not all notes are included on all floor plans.
4. Sheet A2.1; Floor Plan: A Keynote in the elevator references Note 4. Please revise.
5. Sheets A2.1, A2.2, and A2.3; Floor Plan Keynotes: Please indicate that not all notes are included on all floor plans.
6. Sheets A2.1, A2.2, and A2.3; Wall Types: Wall Type B references Details 2, 3, and 9 on Sheet A8.0. Please revise that reference.
7. Sheets A3.1, A3.2, and A3.3; RCP Plan Keynotes: Please indicate that not all notes are included on all RCP plans.
8. Sheets A3.1, A3.2, and A3.3; Reflected Ceiling Plans: Please indicate the exit lighting locations on the plans.
9. Sheet A5.0; North and East Elevations: A Section 7/A9.2 is cut through the sill of upper floor windows. Detail 7/A9.2 is cut at a sill at grade level. Please verify.
10. Sheet S4.0; Section 207: It appears Notes 1 and 2 are reversed. Please verify.
11. General: Please provide written responses to all review comments.:
04/21/2020 SROGERS2 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/02/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide ventilation calculations. Reference: Section 403.1, IMC 2018.
2. Explain how the exhaust fan, EF-1, is providing ventilation to the first and second floors. Reference: Section 107.2.1, IBC 2018.
3. How is ventilation being provided to the third floor? Reference: Section 107.2.1, IBC 2018.
4. Demonstrate energy code compliance for the alterations to the building envelope using calculations based on the current code. Reference: Sections C503.1 and C503.3, International Energy Conservation Code 2018.
06/02/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
06/18/2020 KROBLES1 FIRE REVIEW Needs Review