Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T20CM02306
Parcel: 11706168A

Address:
33 S 5TH AV #205

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM02306
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/29/2020 SAMUEL ROGERS ZONING REVIEW Approved
04/29/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change If the primary heat pump systems (FC-21, FC-22, FC-23 and FC-25) fail, how will ventilation be provided to the space? Reference: Section 403.3.1.1, IMC 2018.
04/29/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
04/29/2020 SROGERS2 ENGINEERING REVIEW Passed
04/29/2020 SROGERS2 BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A1.0; Exiting Plan Second Floor: The Code Review Checklist indicates one exit is required and provided. It appears there is another stair on this floor plan. Please verify.
2. Sheet A1.0; Exiting Plan Second Floor: Please verify the exit access travel distance is from the most remote point of the space (IBC Section 1017.3). Please include the entire second floor for the area for exiting and occupant load.
3. Sheet A1.0; Code Review Checklist: Are the 29 occupants the total occupant load for the second floor? Are the plumbing fixture calculations for the entire second floor? Please verify and revise as required.
4. General: Please provide written responses to all review comments.
04/29/2020 ROBERT SHERRY WATER REVIEW Completed
04/29/2020 SROGERS2 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/29/2020 MARTIN BROWN FIRE REVIEW Approved
05/04/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Provide plans sealed by a registrant registred in the State of Arizona..Per Arizona Revised Statutes.(Electrical).