Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM02306
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/29/2020 | SAMUEL ROGERS | ZONING | REVIEW | Approved | |
04/29/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | If the primary heat pump systems (FC-21, FC-22, FC-23 and FC-25) fail, how will ventilation be provided to the space? Reference: Section 403.3.1.1, IMC 2018. |
04/29/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
04/29/2020 | SROGERS2 | ENGINEERING | REVIEW | Passed | |
04/29/2020 | SROGERS2 | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A1.0; Exiting Plan Second Floor: The Code Review Checklist indicates one exit is required and provided. It appears there is another stair on this floor plan. Please verify. 2. Sheet A1.0; Exiting Plan Second Floor: Please verify the exit access travel distance is from the most remote point of the space (IBC Section 1017.3). Please include the entire second floor for the area for exiting and occupant load. 3. Sheet A1.0; Code Review Checklist: Are the 29 occupants the total occupant load for the second floor? Are the plumbing fixture calculations for the entire second floor? Please verify and revise as required. 4. General: Please provide written responses to all review comments. |
04/29/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
04/29/2020 | SROGERS2 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
04/29/2020 | MARTIN BROWN | FIRE | REVIEW | Approved | |
05/04/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Provide plans sealed by a registrant registred in the State of Arizona..Per Arizona Revised Statutes.(Electrical). |