Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T20CM02301
Parcel: 110120920

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM02301
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/22/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/22/2020 LOREN MAKUS ENGINEERING REVIEW Passed
06/22/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
06/22/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet G01-01; Life Safety Floor Plan: Per the IBC Section 1017.3, the exit access travel distance shall be measured along a horizontal and vertical path. Please revise this plan.
2. Sheet A02-01; Reflected Ceiling Plan: Please indicate the exit lighting on this plan, or reference another sheet for that information.
3. Sheet A07-01; Detail 12: A note near the bottom of this detail references Sheet G02-00 for slab securement. Please revise that reference.
4. Sheet A07-01; Detail 12: A note references Sheet G02.00 for partition type. Please revise that reference.
5. General: Please provide written responses to all review comments.
06/23/2020 STEVE SHIELDS ZONING REVIEW Approved
06/24/2020 JPEELDA1 FIRE REVIEW Approved
06/26/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
06/26/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
06/26/2020 ROBERT SHERRY WATER REVIEW Completed