| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/15/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide full compliance with the 2018 IECC interior and exterior lighting. The current adopted IECC is 2018 not 2012. 2. Provide shielding and color temperature information including manufacture cut sheets for all exterior lighting. 3. Correlate the Mark (RF1 and LX) with the luminaire schedule. 4. Include all the information for shielding and color temperature for all the luminaires with the lumen calculations. Also include the quantities for all exterior luminaires. 5. State which luminaires are exempt from the lumen calculations. 6. Provide a complete description of the scope of work for this project on the plan documents. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements, 2012 Tucson/Pima County Outdoor Lighting Code. |