Permit Number: T20CM02256
Parcel: 13702001C

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T20CM02256
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/14/2020 PETER MCLAUGHLIN PLANNING-CITY HALL REVIEW Approved
04/15/2020 SROGERS2 ENGINEERING REVIEW Passed
04/15/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Monopole Calculations; Page 1 of 2 (Design): Please revise the Building Code to include the 2018 IBC, and revise the wind speed reference to the ASCE-7-10.
2. Construction Drawings: Please include the details and sections that are a part of the monopole calculations into the construction drawings. Include the monopole, the monopole base and anchor bolts, and the pier foundation.
3. General: Please provide the Special Inspection Certificate with Parts A and B completed, This form may be found on the City of Tucson website (www.tucsonaz.gov/PDSD).
04/15/2020 SAMUEL ROGERS ZONING REVIEW Approved
04/15/2020 ERIC NEWCOMB ELECTRICAL-COMMERCIAL REVIEW Needs Review
04/15/2020 MARTIN BROWN FIRE REVIEW Approved
05/07/2020 ARUIZ1 COMMUNICATIONS REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/07/2020 ARUIZ1 OUT TO CUSTOMER Completed