Permit Number: T20CM02249
Parcel: 125120480

Address:
1017 N HOLLY AV

Review Status: Completed

Review Details: OTHER

Permit Number - T20CM02249
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/14/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please assign a branch circuit number for the roof receptacle . Cannot be on the same circuit as the ac unit.2017 NEC 210.63
04/15/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide ventilation calculations for the apartments.
2. Provide a specification for the exhaust fans used for whole house ventilation.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/24/2020 KROBLES1 OUT TO CUSTOMER Completed