Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T20CM02242
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/11/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 01/12/2021 | NICHOLAS ROSS | ZONING | REVIEW | Approved | |
| 12/03/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Overflow scuppers must have the same capacity as the primary scuppers. Reference: 1106.5 and 1108.3, IPC 2018. [Initial comment: Provide secondary (overflow) roof drainage. Reference: Sections 1108.1, 1108.2 and 1108.3, IPC 2018.] 2. Southwest Gas, the local gas utility, only provides natural gas at 7" WG, 2 PSIG, and 5 PSIG. Appliances needing gas service at 7" WG or greater will require a gas meter that delivers at least 2 PSIG gas into a regulator located after the meter set. Reference: Section 402.1, IFGC 2018. [Initial comment: The gas schematic on sheet P2.2 shows the branch pipe for the 4-burner hot plate (53, 120 CFH) as ¾". At a developed length of 125-feet, a 1" branch pipe is required. Reference: Table 402.4 (2), IFGC 2018.] |
| 12/03/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | The make-up air unit piping detail shows a sump drain configuration, not a water recirculation detail. The detail also includes a cross-connection of the water supply and the sump drain. [Initial comment: Verify that the evaporative cooling section of the makeup air unit is equipped with a recirculating water system. Reference: Section 928.2, IMC 2018 and ARS Title 45, Chapter 1, Article 12. See text at: (http://www.azleg.gov/viewdocument/?docName=http://www.azleg.gov/ars/45/00313.htm).] |
| 12/23/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/13/2021 | JGARCIA1 | APPROVAL SHELF | Completed |
| 01/13/2021 | JGARCIA1 | OUT TO CUSTOMER | Completed |
| 01/13/2021 | JGARCIA1 | REJECT SHELF | Completed |