Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T20CM02236
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/13/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. The existing electrical system exceeds 400 amps. Provide complete electrical plans sealed by an Electrical Engineer registered in the State of Arizona. The plans must include all the information as required per the City of Tucson Commercial Plan Submittal Requirements (Electrical), Complete load calcs, luminaire schedule, fault current ratings for the service equipment and downstream equipment, 2018 IECC calcs for the lighting, etc. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |