Permit Number: T20CM02236
Parcel: 13811073B

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T20CM02236
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/27/2020 SAMUEL ROGERS ZONING REVIEW Passed
04/28/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. The existing electrical system exceeds 400 amps. Provide complete electrical plans sealed by an Electrical Engineer registered in the State of Arizona. The plans must include all the information as required per the City of Tucson Commercial Plan Submittal Requirements (Electrical), Complete load calcs, luminaire schedule, fault current ratings for the service equipment and downstream equipment, 2018 IECC calcs for the lighting, etc.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/06/2020 KROBLES1 OUT TO CUSTOMER Completed