Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T20CM02224
Parcel: 11615088L

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM02224
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/14/2020 ELISA HAMBLIN ZONING REVIEW Approved
04/14/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
04/14/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Needs Review To large to walk thru. Please submit.
04/14/2020 EHAMBLI1 ENGINEERING REVIEW Passed
04/14/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet S1.0; General Structural Notes (Note 1): This note indicates that work shall conform to the 2012 International Building Code. Please revise that code.
2. Sheet a1.0 (Floor Plan); Sheet a9.0 (Wall Types): On the east side of Doors 100 and 102, a Wall Type TL is indicated. That Wall Type is not indicated on Sheet a9.0. Please verify.
3. Sheet a1.0; Floor Plan: Two shafts at the south end of Cath Lab 1 and 2 indicate an FX Wall Type. Should these walls be fire resistance rated walls per the IBC Section 713? Please verify.
4. Sheet a1.0; Floor Plan: Two shafts at the north end of Cath Lab 1 and 2 indicate an FX Wall Type. Should these walls be fire resistance rated walls per the IBC Section 713? Please verify.
5. Sheet a1.0; Floor Plan: One shaft at the southwest corner of Cath Lab 2 indicates FX and X Wall Types. Should these walls be fire resistance rated walls per the IBC Section 713? Please verify.
6. Sheet a7.0; Restroom Grab Bars: Please include on this sheet the dimensional location of the grab bars per the ICC/ANSI Figures 604.5.1 and 604.5.2.
7. General: Please provide a Special Inspection Certificate with Parts A and B completed. This may be found at www.tucsonaz.gov/PDSD.
8. General: Please provide written responses to all review commentsl
04/14/2020 ROBERT SHERRY WATER REVIEW Completed
04/14/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Verify that the distance from the hot water source to the hot water termination for the public lavatory complies with the requirements of Section C404.5, IECC 2018.
04/14/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/20/2020 MARTIN BROWN FIRE REVIEW Approved