Review Date Reviewer's Name Type of Review Description Status Comments
05/11/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide more detail on the line diagrams as to the proposed method of performing the PV interconnection. Include all hardware used.
2. Verify that the DG disconnect is suitable for use as service equipment. NEC 690.13C.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements, 2012 Tucson/Pima County Outdoor Lighting Code.