Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T20CM02129
Parcel: 11010279A

Address:
3116 N SWAN RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM02129
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/08/2020 SAMUEL ROGERS ZONING REVIEW Approved
04/08/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
04/08/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
04/08/2020 LOREN MAKUS ENGINEERING REVIEW Passed
04/08/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/08/2020 ROBERT SHERRY WATER REVIEW Completed
04/08/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/08/2020 JVINCEN1 FIRE REVIEW Approved
04/09/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved