Permit Number: T20CM02126
Parcel: 117071920

Address:
702 S 6TH AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM02126
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/23/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
06/23/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide the revised P2.1 sheet. [Initial comment: Correct the note in detail 4/P2.1 that mistakenly refers to WH1 instead of WH2.]
2. Provide the revised P2.1 sheet. [Initial comment: Correct the note in detail 2/P2.1 that mistakenly refers to the detail for WH1being located on P2.1 instead of P3.1.]
3. Provide the revised P2.1 sheet. [Initial comment: Clarify the CW & HW riser diagram 4/P2.1with regard to the water supply to P-1 and P-5.]
4. The civil sheet, C5, does not show a cleanout located prior to the building sewer entering the right-of-way. The plumbing sheet P1.1 however calls for a 2-way cleanout after the cleanouts for the first floor and second floor building drains connect to the building sewer. [Initial comment: Provide a cleanout in the building sewer prior to entering the right-of-way. Reference: Pima County Standard Detail RWRD 401, 2015.]
06/24/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
07/01/2020 LOREN MAKUS ENGINEERING REVIEW Approved
07/20/2020 STEVE SHIELDS ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Steve Shields
Section Manager

PROJECT: T20CM02126 - New Office Building
702 S. 6th Avenue/ C-3 Zoning

TRANSMITTAL DATE: July 20, 2020

DUE DATE: July 22, 2020

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Until DP19-0315 is approved the building plans cannot be approved.

If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package