Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T20CM02125
Parcel: 10321671B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM02125
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/08/2020 SAMUEL ROGERS ZONING REVIEW Approved
04/08/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide ventilation for the two restrooms. Reference: Section 403.1, IMC 2018.
2. Provide ventilation for the training room and changing room. Reference: Section 403.1.1, IMC 2018.
04/08/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
04/08/2020 SROGERS2 ENGINEERING REVIEW Passed
04/08/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Correct the plumbing fixture calculations. Reference Section 2902.1, IBC 2018.
2. Clarify what is meant by the term "tap into existing line…". Reference: Sections 605.5, 702.4, and 707.1, IPC 2018.
3. Provide specifications for the new water closet and lavatory. Reference: Sections 303.4 and 402, IPC 2018
4. Provide cold and tempered water to the new lavatory. Reference: Sections 416.5 and 607.1.2, IPC 2018.
5. Provide a metering faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
6. Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.
04/08/2020 ROBERT SHERRY WATER REVIEW Completed
04/08/2020 MARTIN BROWN FIRE REVIEW Reqs Change On sheet A1.1, please remove general note 5. The fire department does not pre-inspect sprinkler systems to determine code compliance. This would be the responsibilty of the GC and fire sprinkler sub-contractor
04/10/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet T1.1; Code Analysis (Occupancy Load): The occupant load indicates 41 (approximately 32 SF/occupant). Per the IBC Table 1004.5, the maximum floor area allowed per occupant would be 50 (Exercise Room), which would result in a maximum occupant load of 27. The IBC Section 1004.5.1 allows an increase in occupant load if an appeal is submitted to the Building Official. Please verify.
2. Sheet T1.1 (Code Analysis); Sheet A1.1 (Floor Plan): The Code Analysis indicates a point of use water dispenser is required. Where does this show up on the Floor Plan?
3. Sheet A1.1; Floor Plan: Per the IBC Section 1005.7, the Men's restroom door appears to reduce the required minimum egress width of the back exit door. Please verify.
4. General: Please provide written responses to all review comments.
04/10/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed