| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/07/2020 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL FROM: Steve Shields Section Manager PROJECT: Spring Triplex - 2545 E Spring St. T20CM02120 Building Plan TRANSMITTAL DATE: April 7, 2020 1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. A development package meeting the requirements of Administrative Manual 2-06 must be submitted and approved prior to approval of the building plans. 3. Per Unified Development Code (UDC) Table 6.3-2.A: DIMENSIONAL STANDARDS FOR THE R-1, R-2, R-3, MH-1, & MH-2 ZONES, R-2 Zone Nonres Use to Res or Nonres Zone the required perimeter yard setback is 10' or ¾" the height of the exterior wall, greater of the two. Based on plans submitted for a pre-submittal meeting in February of 2020 the proposed triplex does not meet perimeter yard setbacks to the east property line. A Design Development Option (DDO) will need to be submitted and approved prior to approval of the development package and the building plans. 4. The address shown on the foundation plans is not correct. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |
| 04/07/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Needs Review |