Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: WALK THRU - COMM
Permit Number - T20CM02092
Review Name: WALK THRU - COMM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/21/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Plan sheet OeO.2 calls out to provide conduits underground for parking lot lighting. Is this part of the scope of work for this Activity? If not please indicate this on the plan. If it is part of this activity provide more information, such as a pole base detail, grounding, light pole detail, Outdoor Lighting Code compliance if applicable, etc. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements, 2012 Tucson/Pima County Outdoor Lighting Code. |
| 05/21/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed |