Permit Number: T20CM02072
Parcel: 13220007E

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T20CM02072
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/11/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/11/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.

1. Provide more information about the existing system;
(a) Is the existing system equipped with Rapid Shutdown capabilities?
(b) If not, explain how this will be incorporated into the new system.
3. Provide the labeling requirements as required per NEC 690.56C (1),(2),(3).
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements

Final Status

Task End Date Reviewer's Name Type of Review Description
06/19/2020 SBEASLE1 OUT TO CUSTOMER Completed