Permit Number: T20CM01978
Parcel: 129121010

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T20CM01978
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/27/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide a site plan of the parcel showing the location of the proposed 200 amp service including any structures served by this service,
2. Provide a complete electrical line diagram. Include the AIC ratings of the Electrical Service and downstream equipment.
3. Provide a complete description of the scope of work on the plan.
4. If this electrical service is permanent, you complete an appeal for providing a overhead fed service…. The 2018 IBC and amendments require utilities to be installed underground on private property. The waiver form must be completed by the contractor of record or owner of the property and submitted to the permitting staff for processing. This form may be printed off the PDSD website.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements

Final Status

Task End Date Reviewer's Name Type of Review Description
05/21/2020 ARUIZ1 OUT TO CUSTOMER Completed