Review Date Reviewer's Name Type of Review Description Status Comments
06/15/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide more detail as to the proposed electrical work. Electrical demolition and new work.
2. The current adopted electrical code used for commercial electrical compliance is the 2017 NEC. Remove IRC references on the electrical plans and use the current NEC article that apply.
3. Clearly identify all branch circuit and panel designations. For example; on the west exterior wall there is an outlet with (R) 6, 8. What does the (R) stand for.
4. Provide the total lumen count of proposed outdoor lighting compared to allowable lumens. Also identify exterior luminaires with a mark that correlates with the 2012 Tucson/Pima County Outdoor Lighting Code.
5. Provide a complete luminaire schedule.
6. Provide lamp color temperature output for the exterior luminaires and compliance with sec 402.1 (OLC).
7. Locate and identify the panels on the electrical floor plan.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements, 2012 Tucson/Pima County Outdoor Lighting Code, (OLC).
06/15/2020 ROBERT SHERRY WATER REVIEW Completed
06/15/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
06/15/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
06/16/2020 JPEELDA1 FIRE REVIEW Approved
06/19/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved