Permit Number: T20CM01914
Parcel: 135052500

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T20CM01914
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/17/2020 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Section Manager

PROJECT: T20CM01914
6651 E Calle Herculo St
Dining Room & Garage Addition
Residential (1st Review)

TRANSMITTAL DATE: April 17, 2020

The room addition plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

This site is located in the R-1 zone (UDC 4.7.1). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. 10.

1. The site plan shall be drawn at an Engineering scale, i.e. 1" = 10'.

2. This plan is not to scale. If the 105' dimension for the north/south property lines is used to calibrate for measurement than the northern property line is approximately 82' versus 75' and the southern is 91' versus 83.8'

3. Remove the setback lines called out under Site Note 2 and provide setback dimensions from the proposed additions to the applicable property lines

4. Provide a dimension from the center line of Calle Herculo street to the curb and a dimension from the curb to the street property line.

5. Provide a lot coverage calculation on the plan that meets the requirements of Unified Development Code (UDC) Article 6.4.3.

Residential plot plan requirements can be found at https://www.tucsonaz.gov/pdsd/all-application-forms-submittal-requirements.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
04/17/2020 SSHIELD1 ENGINEERING REVIEW Passed
04/21/2020 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change Replace under sized beams with 3-1/8 x 12 GLB; provide gas demand & total length for determining diameter; show arc-fault breakers for new circuits.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/23/2020 AHINES2 OUT TO CUSTOMER Completed