Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T20CM01899
Parcel: 140420740

Address:
7250 S TUCSON BL

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM01899
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/17/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Revise sheet M-4 by removing the COMcheck Mechanical Compliance Certificate. The Building Official has determined that exception (5) of C403.5, IECC 2018 eliminates all of the economizer requirements of C403.5, IECC 2018. Show the IEER for the two 32-ton heat pumps in your equipment schedule. [Initial comment: Replacement of existing HVAC equipment is considered to be new work and as such must comply with the current code requirements. Economizers are required for systems with a cooling capacity greater than 54 MBH or systems with efficiencies 10% greater than the minimum efficiency requirement of Table C403.3.2 (1), IECC 2018. For the two split systems in question, the minimum EER would be 11.2 or an IEER of 12.8. Reference: Exception (5), Section C403.5, IECC 2018.]