Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T20CM01899
Parcel: 140420740

Address:
7250 S TUCSON BL

Review Status: Completed

Review Details: OTHER

Permit Number - T20CM01899
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/27/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Replacement of existing HVAC equipment is considered to be new work and as such must comply with the current code requirements. Economizers are required for systems with a cooling capacity greater than 54 MBH or systems with efficiencies 10% greater than the minimum efficiency requirement of Table C403.3.2 (1), IECC 2018. For the two split systems in question, the minimum EER would be 11.2 or an IEER of 12.8. Reference: Exception (5), Section C403.5, IECC 2018
04/23/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/12/2020 ARUIZ1 OUT TO CUSTOMER Completed